Note: With Gateway 1.10 installed, the NUC takes up to 8 minutes to initialize. The Dell takes just a few minutes.
Symptoms
-
When you are connected to the private network on the LAN2/Gb2 port, the Gateway login screen does not appear. The spinner is stuck.
- You can connect to the private network interface but the public network connection is down and the Gateway application is unreachable.
Resolution
The most likely cause is a network conflict.
-
Make sure your network cables are properly connected.
-
Adjust your network settings to eliminate any network overlap.
-
If you chose a nondefault Gateway appliance private network IP address, make sure the Gateway appliance private network IP address is not part of the DHCP scope; that is, the Gateway's IP address should not fall in the range defined by the DHCP starting and ending IP addresses.
Changes might require restarting the DHCP server.
See How to restart the DCHP server on a Gateway appliance - version 1.1.0 and newer