The Gateway appliance private network IP address is statically assigned 192.168.0.1 by default.
-
Connect a computer to the same private network as the Gateway appliance.
-
Confirm that your computer received a DHCP address from the Gateway. Its address will be 192.168.x.x.
-
Open a browser.
-
Go to https://192.168.0.1 to connect to the Gateway appliance private network and log in.
-
Click Manage Gateway appliance.
-
Select Private network and then Disable DHCP server.
-
Specify the static IP address and subnet mask for your Gateway and click Apply.
Note: Be sure to select a nonroutable IP address scheme.
-