Translate to:
Please select
  • English (English)
  • French (Français)
  • German (Deutsch)
  • Indonesian (Bahasa Indonesia)
  • Italian (Italiano)
  • Portuguese (Português)
  • Russian (Русский)
  • Spanish (Español)
  • Thai (ไทย)
  • Turkish (Türkçe)
  • Vietnamese (Tiếng Việt)
Help
  • Explore Community
  • Get Started
  • Ask the Community
  • How-To & Best Practices
  • Contact Support
Notifications
Login / Register
Community
Community
Notifications
close
  • Forums
  • Knowledge Center
  • Events & Webinars
  • Ideas
  • Blogs
Help
Help
  • Explore Community
  • Get Started
  • Ask the Community
  • How-To & Best Practices
  • Contact Support
Login / Register
Sustainability
Sustainability

We Value Your Feedback!
Could you please spare a few minutes to share your thoughts on Cloud Connected vs On-Premise Services. Your feedback can help us shape the future of services.
Learn more about the survey or Click here to Launch the survey
Schneider Electric Services Innovation Team!

Managing DHCP on the Gateway appliance private network - version 1.10 and newer

EcoStruxure IT Gateway appliance

Support for EcoStruxure IT Gateway Appliances ends in December 2023. Learn how you can migrate to a new installation of the Gateway software.

Enter a search word
    Turn off suggestions
    Enter a search word
      Turn off suggestions
      Enter a user name or rank
        Turn off suggestions
        Enter a search word
          Turn off suggestions
          Enter a search word
            Turn off suggestions
            cancel
            Turn on suggestions
            Showing results for 
            Show  only  | Search instead for 
            Did you mean: 
            Important Note
            • Home
            • Schneider Electric Community
            • EcoStruxure IT Help Center
            • EcoStruxure IT Help Center Categories
            • Gateway
            • EcoStruxure IT Gateway appliance
            • EcoStruxure IT Gateway appliance
            • Managing DHCP on the Gateway appliance private network - version 1.10 and newer
            Options
            • Mark as New
            • Mark as Read
            • Bookmark
            • Subscribe
            • Email to a Friend
            • Printer Friendly Page
            • Report Inappropriate Content
            Invite a Co-worker
            Send a co-worker an invite to the portal.Just enter their email address and we'll connect them to register. After joining, they will belong to the same company.
            You have entered an invalid email address. Please re-enter the email address.
            This co-worker has already been invited to the Exchange portal. Please invite another co-worker.
            Please enter email address
            Send Invite Cancel
            Invitation Sent
            Your invitation was sent.Thanks for sharing Exchange with your co-worker.
            Send New Invite Close

            Related Forums

            • EcoStruxure IT forum

            • APC UPS Data Center & Enterprise Solutions Forum

            Previous Next

            Invite a Colleague

            Found this content useful? Share it with a Colleague!

            Invite a Colleague Invite

            EcoStruxure IT Support

            Submit a support request for additional assistance with EcoStruxure IT software.

            Request Support
            Back to EcoStruxure IT Gateway appliance
            Options
            • Mark as New
            • Mark as Read
            • Bookmark
            • Subscribe
            • Email to a Friend
            • Printer Friendly Page
            • Report Inappropriate Content
            0 Likes
            1363 Views

            Link copied. Please paste this link to share this article on your social media post.

            Trying to translate this page to your language?
            Select your language from the translate dropdown in the upper right. arrow
            Translate to: English
            • (Français) French
            • (Deutsche) German
            • (Italiano) Italian
            • (Português) Portuguese
            • (Русский) Russian
            • (Español) Spanish

            Managing DHCP on the Gateway appliance private network - version 1.10 and newer

            Picard EcoStruxureIT
            ‎2021-02-11 02:22 AM

            The Ecostruxure IT Gateway appliance comes with a DHCP server configured and enabled by default on its private network (LAN2 or Gb2 port on the Gateway appliance depending on the model).

            Access to the Gateway appliance network settings is available on its private network only.

            Do not run more than one DHCP server on the private network.

            If you are deploying the Gateway on a private network that already has a DHCP server, such as from a Data Center Expert server, you must disable the DHCP service on the Gateway or on the other device providing DHCP service.

            If you change the Gateway appliance private network IP address, you must also log in to the CLI on the appliance private network to restart the DHCP server.
            See How to restart the DCHP server on a Gateway appliance - version 1.1.0 and newer

            How to disable the DHCP server on the Gateway appliance

            1. Connect a computer to the same private network as the Gateway appliance..
            2. Open a browser and go to https://192.168.0.1.
            3. Click Manage Gateway appliance and then click the Private network tab.
            4. Select Disable DHCP server. 
            5. Assign a static IP address to the Gateway appliance on the private network.
            6. Click Apply. 
            7. Restart the Gateway DHCP server from the appliance provate network CLI if necessary.

            To re-enable the DHCP server on the Gateway appliance:

            1. Connect a computer to the same private network as the Gateway appliance..
            2. Open a browser and go to https://192.168.0.1 (default) or the IP address you have assigned to the Gateway appliance private user interface.
            3. Click Manage Gateway appliance and then click the Private network tab.
            4. Select Run DHCP server (recommended) and reconfigure the settings for the private network if necessary. 
            5. Click Apply.
            6. Restart the Gateway DHCP server from the appliance private network CLI if necessary.

            Editing DHCP server settings on the Gateway private network

            Configure the DHCP server settings if the Gateway is going to provide DHCP services but you need to change the default settings. For example, change these settings if your private network uses a range of IP addresses different from the default.

            Changes may require that you stop and restart the Gateway DHCP server. If you change the Gateway appliance default IP address to an address that is on a different network, you must also log in to the CLI on the appliance private network to restart the DHCP server. See How to restart the DCHP server on a Gateway appliance - version 1.1.0 and newer

            Access to the Gateway appliance network settings is available on its private network only.

            1. Connect a computer to the same private network as the Gateway appliance.
            2. Open a browser and go to https://192.168.0.1 (default) or the IP address you have assigned to the Gateway appliance private user interface.
            3. Click Manage Gateway appliance and then select the Private tab.
            4. Modify the settings and then click Apply. 

            Default DHCP settings on the Gateway appliance private network

            IP scheme: 1092.168.0.0

            Subnet mask: 255.255.240.0 

            Reserved Gateway IP address: 192.168.0.1

            Starting IP address: 192.168.0.1

            Ending IP address: 192.168.15.254

            Available host IP addresses: 4093

            Was this article helpful? Yes No
            No ratings

            Link copied. Please paste this link to share this article on your social media post.

            Didn't find what you are looking for? Ask our Experts
            To The Top!

            Forums

            • APC UPS Data Center Backup Solutions
            • EcoStruxure IT
            • EcoStruxure Geo SCADA Expert
            • Metering & Power Quality
            • Schneider Electric Wiser

            Knowledge Center

            Events & webinars

            Ideas

            Blogs

            Get Started

            • Ask the Community
            • Community Guidelines
            • Community User Guide
            • How-To & Best Practice
            • Experts Leaderboard
            • Contact Support
            Brand-Logo
            Welcome to Schneider Electric Community!
            Forum-Icon

            You have two options to continue your visit.

            LOGIN / Register

            Why logging in?
            • You enable the complete set of features available, such as posting, sharing, subscribing, private messaging and more.
            • You unlock the access to the whole content that Schneider Electric Community has to offer, including the gated items and the special events.
            And it’s free of charge!!!

            OR

            Continue as a guest

            Terms & Conditions Privacy Notice Change your Cookie Settings © 2025 Schneider Electric

            This is a heading

            With achievable small steps, users progress and continually feel satisfaction in task accomplishment.

            Usetiful Onboarding Checklist remembers the progress of every user, allowing them to take bite-sized journeys and continue where they left.

            of

            Translating the page…
            The page is currently translating. Please wait.
            Auto-suggest helps you quickly narrow down your search results by suggesting possible matches as you type.